Comparison Chart of Water Disinfection Methods
in a Hospital Environment
|
||||||||||||||
|
Item
|
Disinfection System
|
Combination Disinfection Systems | ||||||||||||
|
|
Super Heating & Flush
|
Auto - Chlorinating / Inhibitor
System
|
Auto-Chloramine System (Mono-Chloramine)
|
Chlorine Dioxide
|
Copper-Silver Ionization System
|
OzoniationYes
|
Yes
|
Yes
|
FEASIBLE - RETURN LOOP WITH FIXTURE
/ EQUIPMENT BACK FLOW PREVENTION REQUIRED
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
| USED ON DOMESTIC HOT WATER SYSTEM |
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
Yes
|
||||
| CHEMICAL UTILIZED |
None
|
SODIUM HYPOCHLORITE
|
CHLORAMINE (CHLORINE & AMMONIA)
|
CHLORINE DIOXIDE (SODIUM CHLORITE)
|
COPPER & SILVER (MINERALS)
|
NONE
|
NONE
|
SODIUM HYPOCHLORITE
|
CHLORAMINE (CHLORINE & AMMONIA)
|
CHLORINE DIOXIDE (SODIUM CHLORITE)
|
||||
| BY-PRODUCT |
None
|
TRIHALOMETHANES (THM'S)
|
TRIHALOMETHANES (THM'S) (FAR LESS
THAN CHLORINE)
|
SOME CHEMICAL DECOMPOSITION IN
FORM OF CHLORITE AND CHLORATE
|
NONE
|
BROMATE
|
OZONE
|
TRIHALOMETHANES (THM'S)
|
TRIHALOMETHANES (THM'S) (FAR LESS
THAN CHLORINE)
|
SOME CHEMICAL DECOMPOSITION IN
FORM OF CHLORITE AND CHLORATE
|
||||
| EFFECTIVE MAX. pH |
None
|
7.8 pH
|
9 pH
|
10 pH
|
8 pH
|
NA
|
NA
|
7.8 pH
|
9 pH
|
10 pH
|
||||
| TASTE & ODORS |
None
|
YES - CAN CAUSE TASTE AND ODOR
PROBLEMS
|
YES - CAN CAUSE TASTE AND ODOR
PROBLEMS
|
NONE (BELOW .8 PPM) - REMOVES MOST
TASTE AND ODORS PROBLEMS
|
NONE
|
YES - WILL ADD ODOR
|
NONE - PROVIDED HIGH INTENSITY
OZONE LAMPS ARE NOT USED
|
YES - CAN CAUSE TASTE AND ODOR
PROBLEMS / ONLY IF HIGH INTENSITY OZONE LAMPS ARE USED
|
YES - CAN CAUSE TASTE AND ODOR
PROBLEMS / ONLY IF HIGH INTENSITY OZONE LAMPS ARE USED
|
NONE (BELOW .8 PPM) - REMOVES MOST
TASTE AND ODORS PROBLEMS / ONLY IF HIGH INTENSITY OZONE LAMPS ARE USED
|
||||
| IMPACT ON EQUIPMENT AND SYSTEMS |
Potential
|
POTENTIAL CORROSION PROBLEMS
|
MINIMAL POTENTIAL CORROSION PROBLEMS
|
MINIMAL POTENTIAL CORROSION PROBLEMS
|
MINIMAL POTENTIAL DEPOSITION OF
COPPER ON MILD STEEL / LOCALIZED CORROSION - NONE REPORTED
|
POTENTIAL CORROSION PROBLEMS
|
POTENTIAL - CORROSION PROBLEMS IF
HIGH INTENSITY OZONE LAMPS ARE USED
|
POTENTIAL CORROSION PROBLEMS /
ADDITIONAL CORROSION PROBLEMS IF HIGH INTENSITY OZONE LAMPS ARE USED
|
MINIMAL POTENTIAL CORROSION PROBLEMS
/ ADDITIONAL CORROSION PROBLEMS IF HIGH INTENSITY OZONE LAMPS ARE USED
|
MINIMAL POTENTIAL CORROSION PROBLEMS
/ ADDITIONAL CORROSION PROBLEMS IF HIGH INTENSITY OZONE LAMPS ARE USED
|
||||
| IMPACT ON DIALYSIS EQUIPMENT |
None
|
NONE (BELOW 4 PPM) - CARBON FILTERS
AND RO EQUIPMENT EFFECTIVELY REMOVES CHLORINE AND BY-PRODUCTS
|
SIGNIFICANTLY DIFFICULT TO REMOVE
CHLORAMINES (MONO-CHLORAMINES) AND BY-PRODUCTS AT 4 PPM AND BELOW -
CARBON FILTERS EFFECTIVE, RO MEMBRANE NOT EFFECTIVE, MEMBRANE DAMAGE
|
NONE (BELOW .8 PPM) - CARBON FILTERS
AND RO EQUIPMENT EFFECTIVELY REMOVES CHLORINE DIOXIDE AND BY-PRODUCTS
|
INFORMATION CURRENTLY NOT AVAILABLE
|
INFORMATION CURRENTLY NOT AVAILABLE
|
NONE
|
NONE (BELOW 4 PPM) - CARBON FILTERS
AND RO EQUIPMENT EFFECTIVELY REMOVES CHLORINE AND BY-PRODUCTS
|
SIGNIFICANTLY DIFFICULT TO REMOVE
CHLORAMINES (MONO-CHLORAMINES) AND BY-PRODUCTS AT 4 PPM AND BELOW -
CARBON FILTERS EFFECTIVE, RO MEMBRANE NOT EFFECTIVE, MEMBRANE DAMAGE
|
NONE (BELOW .8 PPM) - CARBON FILTERS
AND RO EQUIPMENT EFFECTIVELY REMOVES CHLORINE DIOXIDE AND BY-PRODUCTS
|
||||
| ENVIRONMENTAL & HEALTH EFFECTS |
WATER IS AT SCALDING TEMPERATURE
|
PRODUCES CARCINOGENIC THM'S.
|
PRODUCES CARCINOGENIC THM'S (less
than chlorine).
|
NONE - DOES NOT PRODUCE THM'S AND
CAN DESTROY SOME THM'S.
|
COPPER IS ACUTELY TOXIC TO MANY
AQUATIC SPECIES AT LEVELS LOW AS 50 PPB. SYSTEM OPERATES BETWEEN 200
- 600 PPB COPPER, 10 TO 60 PPB SILVER.
|
NONE - BROMITE IDENTIFIED AS AN
ANIMAL CARCINOGEN - EFFECTS ON HUMANS UNKNOWN
|
NONE
|
PRODUCES CARCINOGENIC THM'S.
|
PRODUCES CARCINOGENIC THM'S (less
than chlorine).
|
NONE - DOES NOT PRODUCE THM'S AND
CAN DESTROY SOME THM'S.
|
||||
| EPA APPROVED PRIMARY DRINKING WATER DISINFECTANT |
No
|
YES (below 4 ppm)
|
YES (below 4 ppm)
|
YES (below .8 ppm)
|
NO
|
NO
|
NO
|
YES (below 4 ppm)
|
YES (below 4 ppm)
|
YES (below .8 ppm)
|
||||
| BREAKS DOWN BIOFILM (AT NOMINAL OPERATING CONDITIONS) |
Yes
|
NO @ BELOW 50 PPM - MINIMAL ABOVE
50 PPM (SYSTEM OPERATES BETWEEN 2 - 3 PPM)
|
NO - (SYSTEM OPERATES AT 2-3 PPM)
|
YES
|
YES / NO - DEPENDING ON PPM
|
NO
|
NO
|
NO @ BELOW 50 PPM - MINIMAL ABOVE
50 PPM (SYSTEM OPERATES BETWEEN 2 - 3 PPM)
|
NO - (SYSTEM OPERATES AT 2-3 PPM)
|
YES
|
||||
| INHIBITS BIOFILM (AT NOMINAL OPERATING CONDITIONS) |
No
|
MINIMAL
|
MINIMAL
|
YES
|
YES / NO - DEPENDING ON PPM
|
NO
|
NO
|
MINIMAL
|
MINIMAL
|
YES
|
||||
| SHORT TERM RESIDUAL EFFECTIVENESS AGAINST LEGIONELLA (SYSTEM NOT OPERATING) |
YES - (APPROX. ONE WEEK)
|
YES
|
YES - FAR LESS EFFECTIVE AS CHLORINE
|
YES
|
YES
|
NO
|
NO
|
YES
|
YES - (FAR LESS EFFECTIVE AS CHLORINE)
|
YES
|
||||
| LONG TERM RESIDUAL EFFECTIVENESS AGAINST LEGIONELLA (SYSTEM NOT OPERATING) |
None
|
NONE
|
NONE
|
MINIMAL - SOME RESIDUAL PROTECTION
UNTIL BIOFILM IS RE-ESTABLISHED - NONE FOR BULK WATER
|
YES FOR HOT WATER SYSTEMS ONLY
- (LONG TERM STUDIES [4 YEARS] INDICATE LEGIONELLA MAY DEVELOP A TOLERANCE
TO SILVER )
|
NONE
|
NONE
|
NONE
|
NONE
|
MINIMAL - SOME RESIDUAL PROTECTION
UNTIL BIOFILM IS RE-ESTABLISHED NONE FOR BULK WATER
|
||||
| FLUSHING REQUIRED AT ALL FIXTURES AT START UP AND ON PERIODIC BASES |
Yes
|
YES
|
YES
|
YES
|
YES
|
YES
|
YES
|
YES
|
YES
|
YES
|
||||
| CHLORINE SHOCKING OF WATER SYSTEM REQUIRED PRIOR TO SYSTEM OPERATING (SHOCKING EFFECTS BULK WATER ONLY - NO EFFECT ON BIOFILM) |
NA
|
YES
|
YES
|
NOT REQUIRED
|
NOT REQUIRED
|
YES
|
YES
|
YES
|
YES
|
NOT REQUIRED
|
||||
| ESTIMATED FOR A 600 GPM SYSTEM (NOT INSTALLED) |
NA
|
$9,000 (approx.)
|
$9,000 (approx.)
|
$12,000
|
$36,000
|
NOT AVAILABLE
|
$27,000
|
$36,000 (approx.)
|
$42,000 (approx.)
|
$39,000
|
||||
| ESTIMATED INSTALLATION COST |
NA
|
$5,000 (approx.)
|
$5,000 (approx.)
|
$3,000
|
$5,000
|
NOT AVAILABLE
|
$10,000
|
$15,000 (approx.)
|
$15,000 (approx.)
|
$13,000
|
||||
| ESTIMATED ANNUAL MAINTENANCE COST |
$12,500 (PER EVENT)
|
$8,000
|
$8,000
|
$16,650 @ 1 LB CIO2 OR $28,250
@ 2 LBS CIO2
|
$25,250
|
NOT AVAILABLE
|
$12,600
|
$20,600
|
$20,600
|
$20,000 @ 1 LB CIO2 OR
$32,000 @ 2 LBS CIO2 |
||||